Parameters
|
Values
|
Model |
48/10000/140-100/100 |
PowerControl / PowerAssist |
Yes |
Integrated Transfer switch |
Yes |
AC inputs (2x) |
Input voltage range: 187-265 VAC ,Input frequency: 45 – 65 Hz ,Power factor: 1 |
Maximum feed through current (A) |
2x 100 |
Input voltage range (V DC) |
38 – 66 V |
Output |
Output voltage: 230 VAC ± 2% , Frequency: 50 Hz ± 0,1% |
Cont. output power at 25°C (VA) |
10000 |
Cont. output power at 25°C (W) |
8000 |
Cont. output power at 40°C (W) |
6500 |
Cont. output power at 65°C (W) |
4500 |
Peak power (W) |
20000 |
Maximum efficiency (%) |
96 |
Zero load power (W) |
60 |
Zero load power in AES mode (W) |
40 |
Zero load power in Search mode (W) |
15 |
Charge voltage 'absorption' (V DC) |
57,6 V |
Charge voltage 'float' (V DC) |
55,2 V |
Storage mode (V DC) |
52,8 V |
Charge current house battery (A) |
140 |
Charge current starter battery (A) |
NA |
Battery temperature sensor |
Yes |
Auxiliary output (A) |
50 |
Programmable relay |
3x |
Protection |
a - g |
VE.Bus communication port |
For parallel and three phase operation, remote monitoring and system integration |
General purpose com. port |
2x |
Remote on-off |
Yes |
Common Characteristics |
Operating temp.: -40 to +65˚C Humidity (non-condensing): max. 95% |
Maximum altitude |
3500 m |
Common Characteristics |
Material & Colour: aluminium (blue RAL 5012) Protection category: IP 21 |
Battery-connection |
Four M8 bolts (2 plus and 2 minus connections) |
230 V AC-connection |
Bolts M6 |
Weight (kg) |
51 |
Dimensions (hxwxd in mm) |
470 x 350 x 280 |
Safety |
EN-IEC 60335-1, EN-IEC 60335-2-29, EN-IEC 62109-1 |